Well-Known Member
Well as the title says, I'm in the process of laying out the electrical in a new build. I've got 5 rows of 3 lights and if I can get 3 lights on 1 circuit it will make the layout look really clean.
If I run a 20 amp breaker/circuit, and have (3) separate 15mp single outlet receptacles on this circuit, 1 for each light, will I run into any issues because each receptacle is only rated for 15amps? The lights are going to be drawing 4.6amps each at 240v, so technically I'm under the 15amp draw, just wondering if I'm splitting it up over (3) receptacles makes a difference.
I know you will say just go buy a 20 amp receptacle but I've got a ton of these 15amp ones and would like to use them.
If I run a 20 amp breaker/circuit, and have (3) separate 15mp single outlet receptacles on this circuit, 1 for each light, will I run into any issues because each receptacle is only rated for 15amps? The lights are going to be drawing 4.6amps each at 240v, so technically I'm under the 15amp draw, just wondering if I'm splitting it up over (3) receptacles makes a difference.