Electrical help for TWO 5-1000 Watt Light grow rooms:

cj0628

Active Member
I'm looking to get a new house probably 3 maybe 4 bedrooms.
after i get my Legal plant count upgrade... I want to run a sealed grow room, AC, Fans,Dehumidifier and Co2 and 5-1000 Watt Grow lights in 2 rooms. I know i will need to call a electrician to help setup and upgrade the AMPS to the house, but im a noob to the electricity haha do i need a certain size house to have that much wattage in one house?? or is it all good if the electrician comes and upgrades my AMPS and circuit panels? i know he will charge a arm and a leg for it but thats the sacrifices haha
 

covert222

Well-Known Member
Easy as fuck. Put a 50 in your breaker box for each room then you get your lights that either run off 240v or jump 110s off of them for everything. Cost you about 200 bucks for the wire and everything
 

Ou8aCracker2

Well-Known Member
So you're looking to do 5x 1kw lights in each room,10kw total?

At 110v that's 90.9 amps!

When running continuous loads (devices run 3 hours or longer) you can only safely use up to 80% of your circuit per breaker.

You'll need some serious electric!

At 240v each 1kw light will draw 4.5 amps each,that's 45.5 amps.

If it were me I'd have each room wired up 240v and a 30 amp breaker for every five 1kw lights.
 

SnapsProvolone

Well-Known Member
I would add amps for cooling and dehumidification. Pull wire for 60 amps imho, set a subpanel to feed lighting controller and hvac. You can only use 80% of breaker ampacity.
 

Ou8aCracker2

Well-Known Member
Yes,I should of added that my last post was only accounting for lighting and lighting only.Not the serious amount of air conditioning,pumps,timers,fans,co2 generator etc.
 

Ou8aCracker2

Well-Known Member
And 60 amps will only be good for all 10kw of lighting only as 80% of 60 amps is 48 amps and that's if going 220/240.

If going 110/120 he'll need even more.

10000/110 = 90.9 Amps and at 80% safeload of breaker capacity is 72.72 amps!
 

Ou8aCracker2

Well-Known Member
For lights and air conditioning,dehumidifiers,humidifiers wire everything up 220/240,for fans and pumps wire 110/120
 

SnapsProvolone

Well-Known Member
And 60 amps will only be good for all 10kw of lighting only as 80% of 60 amps is 48 amps and that's if going 220/240.

If going 110/120 he'll need even more.

10000/110 = 90.9 Amps and at 80% safeload of breaker capacity is 72.72 amps!
Subpanel per 5k room should have stated that.
 

covert222

Well-Known Member
Should have plenty of other outlets available to plug in an air conditioner. The thirty should just be for lights. 240 X 30= 7200. 7200 x.8 = 5760. Puts you there with plenty to spare
 

Ou8aCracker2

Well-Known Member
Should have plenty of other outlets available to plug in an air conditioner. The thirty should just be for lights. 240 X 30= 7200. 7200 x.8 = 5760. Puts you there with plenty to spare
But you should use 220v as a safe measure...

1000w/240v = 4.16667 Amps and 4.16667Amps x 240v = 1000w but doesn't take into account the extra 10% to 15% power the ballast consumes.
 

covert222

Well-Known Member
If you run a five slot square d you could put em all on their own 15 or 20 or whatever maybe just stagger your start up times about 5 or 10 minutes
 

SFguy

Well-Known Member
Yep just had a 30 done for 200 bucks
Sweet man u have him run some 220 also??

So you're looking to do 5x 1kw lights in each room,10kw total?

At 110v that's 90.9 amps!

When running continuous loads (devices run 3 hours or longer) you can only safely use up to 80% of your circuit per breaker.

You'll need some serious electric!

At 240v each 1kw light will draw 4.5 amps each,that's 45.5 amps.

If it were me I'd have each room wired up 240v and a 30 amp breaker for every five 1kw lights.
Sounds like you know your shit man stop by my thread and check it out I just put in a new panel with 220v for my lights in process right know still have to wrap the room with reflectix and serum my intake should be roll withing the next week or two

If you run a five slot square d you could put em all on their own 15 or 20 or whatever maybe just stagger your start up times about 5 or 10 minutes
how would that work??? I still need to change the breaker out to a quad breaker instead of two doubles that I got in place right now my electrician friend left all his tools/toolbox so I KNOW HES COMING BACK AHAHA...
 