Hi
I have a few Q's regarding my setup and the Electric, I'm from the UK so everything is on 240v.
In my room I will be running 4 x 1000w HID lamps, Load split evenly over 2 separate double Plugs either side of the room.
All on 1 32A RCD/MCD breaker, I will also have a multitude of osc fans and duct fans amounting to about 400 watts worth.
Then I will have 1 or 2 1000w oil radiators on at lights off.
My questions,
Is the 32A breaker's limit 7600w? 7600/240 = 32.08 or there abouts
If I was too only want to be using MAX 80% of the 32A, So would that be roughly 6000w available at a safe level?
If I time my oils rads to only come on once all lights have gone off, Should it be fine?
Most the time I will be using 2 x 1kw and 2 x 600w, But there will be a few weeks where they overlap and I'm using all 4x1kw at once for 12 hr periods, I just want to sleep well at night
Thanks guys!
I have a few Q's regarding my setup and the Electric, I'm from the UK so everything is on 240v.
In my room I will be running 4 x 1000w HID lamps, Load split evenly over 2 separate double Plugs either side of the room.
All on 1 32A RCD/MCD breaker, I will also have a multitude of osc fans and duct fans amounting to about 400 watts worth.
Then I will have 1 or 2 1000w oil radiators on at lights off.
My questions,
Is the 32A breaker's limit 7600w? 7600/240 = 32.08 or there abouts
If I was too only want to be using MAX 80% of the 32A, So would that be roughly 6000w available at a safe level?
If I time my oils rads to only come on once all lights have gone off, Should it be fine?
Most the time I will be using 2 x 1kw and 2 x 600w, But there will be a few weeks where they overlap and I'm using all 4x1kw at once for 12 hr periods, I just want to sleep well at night
Thanks guys!