(Yep, sounds great.)
Thanks AL your the man will do 250watt for mums
(Way too much CFL. Clones don't need to be pounded with light, they only need to be convinced it's daylight for 18+h/day. Swap that 105W unit for 2-3 ordinary grocery store 10-20W CFLs, enough of them that all leaves are within about 100mm of a lamp tube. The 105W unit might be useful vegging mums.)
Will use the 105w also in conjunction with 250 MH
(A ventilation system needs to be able to shift the room's airmass in about 3 mins. Calculate your room volume in cubic feet and divide by 3. That's the minimum CFM rating for the ventilation system. More is gooder.)
OK Al here the tricky part my closet for mums/clones is 88"Hx 24"Wx 24"D that is converted in feet's 7.33Hx2.00Wx2.00D that will = 29.32 cu ft / 3 = 9.77 CFM ? is that right I don't think so need help in that dept lol also flowering closet 88"Hx 60"Wx 24"D convert 7.33Hx5.00Wx2.00D= 73.30 sq ft/ 3= 24.43????
(If a single exhaust blower (with passive intake/s, which combined are double the area of the exhaust diameter i.e. 6" blower needs 2x 6" dia intake holes) has to do all the work, increase the CFM rating to 1CFM per cu ft of room airmass, i.e. 200 cu ft room gets a 200CFM exhaust.)
So should get for mum/clones minimum CFM rating 30 cfm? and flowering 75 cfm?
(Remember that axial blowers don't work well into high static pressures caused by carbon filters or long ducts with a lot of bends. Use a centrifugal blower for cases like this. An axial will not get anywhere near its free-air CFM rating when pushing into obstructive loads.)
OK centrifugal blowers it is thanks Al
(Intake blowers can always be axials. The room airmass will be at a slightly negative pressure due to the exhaust removing air from the room, meaning the intakes are not pushing into a high static pressure.)
OK so I should get a axials intake blower?
(Intake blowers should be rated at about 80-90% of the exhaust blower's CFM rating. This keeps the room at a slightly negative pressure referenced to atmosphere. Any air leaks in your construction will leak air inward rather than out, so all air leaving the op is going through your exhaust blower (and filter if present), making scents easier to control.)
Wow nice so multiply the cfm of exhaust blower by 80-90% and that the cfm intake I should get?
(It's a rough rule of thumb but 50W of HPS light per sq ft will do. Calculate the area of your intended lighted floorspace in sq ft and multiply by 50. There's your lamp size in watts (or close to it).)
This is the part that sucks my flower closet has a available grow space of 4.57' x 2.0'=9.14 feet x 50= 457 so I guess a 400watter but I want nice big buds can i still run a 600 air cooled tube?
(The only air-cooled reflector worth having is a cooltube.
Avoid the box-type 'Euro hood' reflectors. These sometimes don't have intake air duct flanges, may not have a glass cover over the lamp or may only have 100mm duct holes. It's necessary to have a fully closed air path for lamp cooling air and 100mm is too small for anything but a 400. Boxy reflectors are also quite inefficient; they bounce a lot of light right back at the lamp tube.
Double parabola type 'batwing' reflectors put very nearly all reflected light on the plants instead of back on the tube.
Cooltubes encase the lamp in glass, which is thermally resistive. They also keep the airflow smooth and very close to the lamp, meaning most of the lamp's heat is leaving with the airflow instead of being allowed to warm the fixture and lose heat by convection into the room's airmass.)
Yea exactly that the cool tube I was thinking of getting but in 600 watt I guess for something like that is gonna need a blower also to cool the bulb? and if you would know what size?
(I don't see where your need for an MH is. If you're going to do SoG, you won't be vegging any plants aside from mums and the 250HPS will do fine for for that.