Hi,
I want to know If with my setup my lamps will run at full power or if my electrical installation will be inefficent.
Ok my setup:
I have four 750W Double ended lamp fixtures.
My plan was to put two lamps at one circuit. That would mean two circuits for all four lamps.
I have 16 amp breakers and 220 volts. (On circuit would be technically strong enough for 3520 Watts?)
The cables are equivalent to 16 AWG or 1,5mm^2 in metric.
The length of the cables to the lamp fixtures (including the length of the cables of the lamps ballast itself) would be... I guess... maximum 20 meters.
Now the problem I worry about:
I did read, if the cable is too long and/or the cable to thin, you would get a voltage drop. I did read that a voltage drop of 10 % causes the lamp to work only at 70% (I am not sure if I remember this piece of information technically correct, but I understood that a voltage drop would be pretty bad)
So now my question:
At what length of cable and thickness I have to expect a drop in voltage? (I have 220volts)
Do I need to install 14 AWG cables instead?
I want to know If with my setup my lamps will run at full power or if my electrical installation will be inefficent.
Ok my setup:
I have four 750W Double ended lamp fixtures.
My plan was to put two lamps at one circuit. That would mean two circuits for all four lamps.
I have 16 amp breakers and 220 volts. (On circuit would be technically strong enough for 3520 Watts?)
The cables are equivalent to 16 AWG or 1,5mm^2 in metric.
The length of the cables to the lamp fixtures (including the length of the cables of the lamps ballast itself) would be... I guess... maximum 20 meters.
Now the problem I worry about:
I did read, if the cable is too long and/or the cable to thin, you would get a voltage drop. I did read that a voltage drop of 10 % causes the lamp to work only at 70% (I am not sure if I remember this piece of information technically correct, but I understood that a voltage drop would be pretty bad)
So now my question:
At what length of cable and thickness I have to expect a drop in voltage? (I have 220volts)
Do I need to install 14 AWG cables instead?