I've got an interesting issue and I wanted to reach out to see if anyone could help with info. I've surely ran out of ideas!
Current Setup: Ideal Air 180 pint. 4 ton AC Unit (Air Handler).
I've got 3 rows, and I've got 3 ducts for each row. The ducts are setup to point into the back of the room. My cold air gets dumped into the back, then gets pulled to the front via the air handler. The thermostat for the unit is in the front of the room. My Dehu is setup in the front of the room. see the attached image.
My issue is that the thermostat has a 3 minute response rate to the air handler which turns the AC on or off. For example, if I set the temperature to 81, the AC will turn on at 86 and turn off at 77. This is causing my room to get warm, and cold frequently. It's not creating a stable environment. At the same time the AC fan doesn't have an option to turn off, it is continuously running on either auto or low. This is causing my humidity to rise which in return is causing my dehu to work more.
My theory as of now is that when the AC is done cooling, the fan continues to run. This is causing the humidity to rise in the room, which turns the Dehu on. When the dehu is on, it's creating heat in the room and then forcing the AC to to turn on. When the AC turns on the humidity goes down, the dehu turns off, but once again the AC fan continues to run causing rise in humidity and the cycle continues.
-Can't turn the fan off, only ON or Auto
AC Thermostat is set to 81 and dehu is set to 55
While the lights are off here is the activity of the middle of the room.
2:07 PM - 74 degrees 74% humidity
2:23 PM - 80 degrees 64% humidity
2:30 PM - 81 degrees 65% humidity
2:35 PM - 81.6 degrees 63% humidity
2:36 PM - 81 degrees 63% humidity
2:43 PM - 75 degrees 67% humidity
2:45 PM - 73.8 degrees 67% humidity
2:46 PM - 73.6 degrees 72% humidity
2:50 PM - 74.4 degrees 74% humidity
3:05 PM - 80 degrees 65% humidity
3:12 PM - 81 degrees 65% humidity
3:15 PM - 81 degrees 65% humidity
3:20 PM - 78.8 degrees 65% humidity
3:23 PM - 76 degrees 66% humidity
3:30 PM - 74 degrees 73% humidity
Current Setup: Ideal Air 180 pint. 4 ton AC Unit (Air Handler).
I've got 3 rows, and I've got 3 ducts for each row. The ducts are setup to point into the back of the room. My cold air gets dumped into the back, then gets pulled to the front via the air handler. The thermostat for the unit is in the front of the room. My Dehu is setup in the front of the room. see the attached image.
My issue is that the thermostat has a 3 minute response rate to the air handler which turns the AC on or off. For example, if I set the temperature to 81, the AC will turn on at 86 and turn off at 77. This is causing my room to get warm, and cold frequently. It's not creating a stable environment. At the same time the AC fan doesn't have an option to turn off, it is continuously running on either auto or low. This is causing my humidity to rise which in return is causing my dehu to work more.
My theory as of now is that when the AC is done cooling, the fan continues to run. This is causing the humidity to rise in the room, which turns the Dehu on. When the dehu is on, it's creating heat in the room and then forcing the AC to to turn on. When the AC turns on the humidity goes down, the dehu turns off, but once again the AC fan continues to run causing rise in humidity and the cycle continues.
-Can't turn the fan off, only ON or Auto
AC Thermostat is set to 81 and dehu is set to 55
While the lights are off here is the activity of the middle of the room.
2:07 PM - 74 degrees 74% humidity
2:23 PM - 80 degrees 64% humidity
2:30 PM - 81 degrees 65% humidity
2:35 PM - 81.6 degrees 63% humidity
2:36 PM - 81 degrees 63% humidity
2:43 PM - 75 degrees 67% humidity
2:45 PM - 73.8 degrees 67% humidity
2:46 PM - 73.6 degrees 72% humidity
2:50 PM - 74.4 degrees 74% humidity
3:05 PM - 80 degrees 65% humidity
3:12 PM - 81 degrees 65% humidity
3:15 PM - 81 degrees 65% humidity
3:20 PM - 78.8 degrees 65% humidity
3:23 PM - 76 degrees 66% humidity
3:30 PM - 74 degrees 73% humidity
Last edited: