Hey guys, I'm stumped here, I figured I did all the math correctly before setting things up but I'm getting this circuit tripping once a week or so.
I have a 1000w + 600w on a 15 amp circuit. The dimmable ballasts say they pull 8.4 amps and 5.6 amps respectively. That adds up to 14 amps on the 15 amp circuit...
So why would it trip? I'm 1 amp under and I doubt the extra startup juice exceeds an amp. The first time it tripped it wouldn't happen until both lights were on for 3-4 hours or so...
Now here is the very strange part...Today at 4am (looking at the timers) the breaker tripped. Neither light turns on until 8am...and they only run until midnight. ZERO power is being pulled on that circuit at 4am...
The only thing in the whole house that runs at 4am is a 1100w window a/c unit that turns on/off every 30 minutes. However, this is on its own separate 15 amp circuit...
HELP please!