I want to put 2 600's + an intake in a 4x4/5x5 tent(havent decided). Can I do it without having to rewire/hire dirty electritian etc.
If it is on a 20 amp breaker and your wiring is rated for that load yes...check out bored electricians posts or send him a messageI want to put 2 600's + an intake in a 4x4/5x5 tent(havent decided). Can I do it without having to rewire/hire dirty electritian etc.
I thought the rule was to use only 80% for fire safety?Yes. How many watts does he intake use? The lowest amps on a circuit is gonna be 15. 15 @ 110v = 1,650watts. 15 @ 230v = 3,450 watts.
1,650 watts > 1,280watts~ + Intake
this is completely wrong.Yes. How many watts does he intake use? The lowest amps on a circuit is gonna be 15. 15 @ 110v = 1,650watts. 15 @ 230v = 3,450 watts.
1,650 watts > 1,280watts~ + Intake
I run 2x600 + fans on one 15A circuit, but I make sure to spread the load around to as many outlets as possible, probably me just being paranoid.I want to put 2 600's + an intake in a 4x4/5x5 tent(havent decided). Can I do it without having to rewire/hire dirty electritian etc.
thats if you know there is nothing else on that circuitthis is completely wrong.
15a @ 110v = 1650w
7.5a @ 220v=1650w
the wattage NEVER changes, only the amperage or voltage....
80% of 1650w= 1320w MPF (max power factor)
2 x 600w = 1200w (lights)
1 x 100w = 100w (fans & timers/relays)
1200w + 100w = 1300w= 10.83 FLA (full load amperage)
1300w FLA < 1320w MPF
your cutting it close, but it will be fine by any industry standard or code...
you could get away with an additional 200w or so for intermittant use when the lights are on...thats if you know there is nothing else on that circuit
Damn so what'll that be for this lesson? 20$this is completely wrong.
15a @ 110v = 1650w
7.5a @ 220v=1650w
the wattage NEVER changes, only the amperage or voltage....
80% of 1650w= 1320w MPF (max power factor)
2 x 600w = 1200w (lights)
1 x 100w = 100w (fans & timers/relays)
1200w + 100w = 1300w= 10.83 FLA (full load amperage)
1300w FLA < 1320w MPF
your cutting it close, but it will be fine by any industry standard or code...
Hey electrician dude whats up quick question....what are the reseptacles in a backyard usually rated at ? outdoor receptacle ?and another question...within the outdoor receptacle there is two outlets are each of those 110 ?