THanks, its a 120volt circuit.
Basically what I want to do is seperate the outlet to the right of the picture (which has the black and white wire coming out) on its own circuit from the grey romex.
Then Ill also be running another outlet down from the romex circuit.
What Im doing is making it so I have two seperate 20amp 120volt circuits in one room.
So I ran the romex along the rafters to this junction box from the subpanel.
So what your saying is to connect teh black and white wires from the right to the romex.
What do I do with the ground wire coming out of the romex?
Can I hook it through that little hole in the junction box to suffice as ground?