S sourdieselyumyum Well-Known Member Oct 9, 2019 #1 Can I wire in a 30 amp dryer plug cord to a 8 light controller rated for 50 amps if I only run 6 lights at 2.5 amps each so 15 amps total at 240v? or would there be a problem? it would be on a 30 amp breaker
Can I wire in a 30 amp dryer plug cord to a 8 light controller rated for 50 amps if I only run 6 lights at 2.5 amps each so 15 amps total at 240v? or would there be a problem? it would be on a 30 amp breaker
S sourdieselyumyum Well-Known Member Oct 13, 2019 #3 Renfro said: Yes Click to expand... so yes to itll be fine or yes to it'll cause a problem lol
Renfro Well-Known Member Oct 13, 2019 #4 sourdieselyumyum said: Can I wire in a 30 amp dryer plug cord to a 8 light controller rated for 50 amps... it would be on a 30 amp breaker Click to expand... Yes
sourdieselyumyum said: Can I wire in a 30 amp dryer plug cord to a 8 light controller rated for 50 amps... it would be on a 30 amp breaker Click to expand... Yes
Renfro Well-Known Member Oct 13, 2019 #5 Your not exceeding any limitations, a 50 amp controller can be run on a 30 amp breaker with up to 24 amps load.
Your not exceeding any limitations, a 50 amp controller can be run on a 30 amp breaker with up to 24 amps load.