spencer2121
Well-Known Member
I just double checked again to make sure and yeah unfortunately they run on the same breakerThe lights are on the same breaker as the room they are in, but that would be such a simple solution!
I just double checked again to make sure and yeah unfortunately they run on the same breakerThe lights are on the same breaker as the room they are in, but that would be such a simple solution!
I'm assuming this is sarcastic, but just to clarify... Don't do this HAHA.Just replace the 15 amp breaker with a 20 amp breaker... just make sure u don't put anymore load on it than the AC and light. Why does this have to be so complicated, geez
Actually, I am serious. 14-2 wire will be okay with 20 amp breaker as opposed to a breaker being overloaded. Is it a good idea? Probably not. But it is better than running the breaker at 15.8 amps. Again, assuming that NOTHING ELSE is put on that breaker -at that's where the danger really lies :/I'm assuming this is sarcastic, but just to clarify... Don't do this HAHA.
I upgraded one to 20, no problem. 14-2 wire aint gonna arc out at 16 amps. By the way, it was a local electrician friend of mine that told me I could if I needed to. Since then I ran several dedicated lines but I'm sure running 15.8 through 15 amp breaker is much better ideado not do that upgrading the breaker yes will solve the problem of not tripping breaker but now you run risk of fire in the walls that house the wire, now bieng overheated because you now can run 20 amps of power they have the breakers for a reson better to isolate problem to panel and replace breaker every once in awhile than worry if the wire is getting too hot in the walls p.s. if you take gagekkos advice make sure you replace all the batteries in your smoke detectors because you will need them