buggin69
Active Member
to add to the last post... Do I need to run 4 seperate lines from each side of the double 20A breaker, to each 240v outlet... or can we run 1 line from each and parrallel them along to each other outlet... hope that makes sense...
-Mitus
you can go from box to box... outlet to outlet... but you have to get the two wires coming from the double 20 breaker to each side of the 240 receptacles (the gold colored screws)
EDIT::
you can not go from white to black, white to black... like you can with 120
you'll have to carry both legs to each receptacle... but you do not have to run 4 lines all teh way back to the sub-panel