Would a setup like this be too much for a second floor of a house to hold that much water? Plan on putting a 150gallon RO res and two 50 gallon mix tanks in my bathroom upstairs would that be too heavy?
A us gallon of water weighs just over 8 lbs so its quite a bit more than a UK gallon.Every pint weighs a pound or every litre a kilogram.
250 UK gallon would be around 1.25 tons if my figures are correct.
yeh does sound sketch haha I prob won’t try n riskThat's over 2,000lbs of water assuming all three tanks are full. I'm not sure what the standard load limit for a residential second floor is though. I do know a standard bathtub is about 42 gallons so it would be like putting 6 bathtubs in your bathroom. Seems sketch.
A UK gallon is 5 litres so 5kg /11lbsA us gallon of water weighs just over 8 lbs so its quite a bit more than a UK gallon.
Quick google search states that 30 or 40 lbs per square foot is standard in newer construction. So yeah, Thats probably not safe.yeh does sound sketch haha I prob won’t try n risk
It then n do two 50 gallon tanks or something