canadiancracker
Active Member
i have a 8x10.5x8foot room with 4 1000w hps hortilux aircooled with 2x6" one for intake and exaust, and a 737cfm 8" exaust turbine, 4" 90cfm intake fan with 60degree intake air temp, and my room still gets a little to hot, it runs around 80degrees or so. my exaust is pulling not pushing and everything is air tight, i have a very loud exaust outside cause of this and i still cannot keep the temps at 72degrees,
my options now are
1- add ac in room
2- change one of the 6" turbines into the rooms intake(for a faster air change time)
3- air cool only 2 lamps per 6" turbine(i have all 4 on the same ducting in a big U)
4- add co2, i already have a genator i would just have to fork out the huge chunk of change for a controller...
5-add insulated ducting insted of aluminumized shit..
whats my best option? or input any if you have better ideas,
thanks in advance.
my options now are
1- add ac in room
2- change one of the 6" turbines into the rooms intake(for a faster air change time)
3- air cool only 2 lamps per 6" turbine(i have all 4 on the same ducting in a big U)
4- add co2, i already have a genator i would just have to fork out the huge chunk of change for a controller...
5-add insulated ducting insted of aluminumized shit..
whats my best option? or input any if you have better ideas,
thanks in advance.