Ac infinity cloudline T6 controller stops working when 1000w HPS turns on.

ZellzGarden

Member
Im hoping a new ballast will fix it too
I had the same issue, if you put your controller on a UPS to clean and power interference from the ballast it will start working again. You can test this by plugging the controller into an extension cord and put it on a different circuit (breaker). I hope this work for you..
Hello all so I have a conundrum here.

My T6 works perfectly fine until the HPS clicks on, The temp controls stop working and it no longer displays the temp and humidity.
I thought this was an issue with the controller so got in touch with support and replaced it but the issue is still occurring.

I moved the controller as far away from the ballast (electronic) as I could to no evail as well.

The HPS is on its own plug albeit still connected to junction box but I don't believe it's a wattage issue as a 1500w heater was running before on the same power strip as the fan with no issue.

I took a couple photos to show what's happening (i couldn't find a video format that would work) hopefully someone here knows what's going on as ACI support is as stumped as me.
So I plugged into another circuit and it worked so I thought what if I just plug into another outlet in the garage and I did and it worked so something was getting all funky with the surge protector it was on when I turned on the HPS just gonna keep the new ballast tho cause it needed it.
Thanks for everyone's help here.
 

Kaldx7

New Member
So should i get the T6 if im planning to use hps/mh or still the cotroller wouldnt work? Is there any alternative i can hook to the ac infinity inline fan?
 

ForTheNod

Active Member
Hello all so I have a conundrum here.

My T6 works perfectly fine until the HPS clicks on, The temp controls stop working and it no longer displays the temp and humidity.
I thought this was an issue with the controller so got in touch with support and replaced it but the issue is still occurring.

I moved the controller as far away from the ballast (electronic) as I could to no evail as well.

The HPS is on its own plug albeit still connected to junction box but I don't believe it's a wattage issue as a 1500w heater was running before on the same power strip as the fan with no issue.

I took a couple photos to show what's happening (i couldn't find a video format that would work) hopefully someone here knows what's going on as ACI support is as stumped as me.
It does it with hps the probe thing that’s what the customer service told me
 